PV1, PV2, PV1ng-LS, PV2ng -LS

(TU U 27.3-38456790-014:2019)
Copper wires with polyvinylchloride insulation
PV1, PV2, PV1ng-LS, PV2ng -LS

Cord marking does not specify the copper core
P Wire
В Polyvinylchloride plasticate insulation
1 Core (flexibility class 1)
2 Core (flexibility class 2)

ng-LS

Non-combustible, reduced smoke and gas release

Operating and installation requirements

  • Ambient temperature from –40°C to 50°C.
  • Relative humidity up to 100% at temperatures up to 35°C.
  • Recommended temperature at mobile operation not lower than –15°C.
  • Long-term permissible core heating temperature during operation should not exceed 70°C.
  • Rated alternating voltage up to 450/750 V.
  • Warranty service life is 2 years.
  • Service life is minimum 15 years

Wires intended use
PV1, PV2, PV1ng-LS, PV2ng -LS

Wires are intended for a permanent laying within lighting and power networks, as well as for installation of electrical equipment, machines, mechanisms and machining units designed for up to 450 V nominal voltage (up to 450/750 V for networks) and up to 400 Hz frequency or up to 1000 V DC voltage.

Used for installation of electric circuit sections subject to cord bends. Used in all spheres of production and industry as well as for wiring installation. For outdoor wiring it is recommended to use trays, ducts and cable troughs, which protect cords from mechanical damage and ultraviolet radiation

Conductor design
PV1, PV2, PV1ng-LS, PV2ng -LS

Core count Main cores nominal cross-section, mm2
1 1 - 10
Core count Main cores nominal cross-section, mm2
1 10 - 95

Design data for
PV1, PV2, PV1ng-LS, PV2ng -LSwires

Core nominal cross-section, mm2 Nominal radial insulation thickness, mm Maximum outer diameter, mm Maximum conductor resistance at 20°C, Ohm/km Minimum value of insulation resistance at 70°C, MOhm/km Calculated mass of 1 km cord, kg
PV1
1 0,6 2,7 18,1 0,012 14
1,5 0,7 3,2 12,1 0,011 19
2,5 0,8 3,9 7,41 0,009 30
4 0,8 4,5 4,61 0,007 44
6 0,8 4,9 3,08 0,006 63
10 1,0 6,4 1,83 0,0056 105

Note: Calculated and nominal data can deviate from the actual data.
IIdentification markings meet fire safety requirements under DSTU 4809:2007
PV1 – PB 100000000
PV1ng-LS – PB 123111000