PV3, PV3ng-LS

(TU U 27.3-38456790-014:2019)
Copper core cords with polyvinylchloride insulation
PV3, PV3ng-LS

Cord marking does not specify the copper core
P Cord
V Polyvinylchloride plasticate insulation
3 Core (flexibility class 5
ng-LS Non-combustible, reduced smoke and gas release

Operating and installation requirements

  • Ambient temperature from –40°C to 50°C.
  • Relative humidity up to 100% at temperatures up to 35°C.
  • Recommended temperature at mobile operation not lower than –15°C.
  • Long-termpermissiblecoreheatingtemperatureduringoperation should not exceed 70°C.
  • Rated alternating voltage up to 450/750 V.
  • Warranty service life is 2 years.
  • Service life is minimum 15 years.

Wires intended use
PV3, PV3ng-LS

Wires are intended for permanent laying within lighting and power networks, as well as for installation of electrical equipment, machines, mechanisms and machining units designed for up to 450 V nominal voltage (up to 450/750 V for networks) and up to 400 Hz frequency or up to 1000 V DC voltage.

Used for installation of electric circuit sections subject to cord bends. Used in all spheres of production and industry as well as for wiring installation. For outdoor wiring it is recommended to use trays, ducts and cable troughs, which protect cords from mechanical damage and ultraviolet radiation.

Conductor design
PV3, PV3ng-LS

Core count Main cores nominal cross-section, mm2
1 0,5 - 120

Design data for
PV3, PV3ng-LSwires

Core nominal crosssection, mm2 Nominal radial insulation thickness, mm Maximum outer diameter, mm Maximum conductor resistance at 20°C, Ohm/km Minimum value of insulation resistance at 70°C, MOhm/km Calculated mass of 1 km cord, kg
PV3
0,5 0,6 1,9 39,0 0,013 9
0,75 0,6 2,1 26,0 0,011 11
1 0,6 2,2 19,5 0,010 14
1,5 0,7 2,8 13,3 0,010 20
2,5 0,8 3,3 7,98 0,0095 31
4 0,8 3,9 4,95 0,0078 47
6 0,8 4,4 3,30 0,0068 66
10 1,0 6,5 1,91 0,0056 110
16 1,0 8,1 1,21 0,0046 167
25 1,2 9,9 0,78 0,0044 254
35 1,2 11 0,554 0,0038 347
50 1,4 12,5 0,386 0,0037 492
70 1,4 14,5 0,272 0,0032 683
95 1,6 17,0 0,206 0,0032 907
120 1,6 18,7 0,161 0,0029 1131

Identification markings meet fire safety requirements under DSTU 4809:2007
PV3 – PB 100000000
PV3ng-LS – PB 123111000