Nominal cross section of the strand, mm2 | Nominal radial thickness of insulation, mm | The maximum resistance of the conductor at a temperature of 20ºC, Ohm/km | ||
PV1*,
PV1ng |
PV2**
PV2ng |
PV3***
PV3ng |
||
0,5 | 0,6 | 36,0 | – | 39,0 |
0,75 | 0,6 | 24,5 | – | 26,0 |
1,0 | 0,6 | 18,1 | – | 19,5 |
1,5 | 0,7 | 12,1 | 12,1 | 13,3 |
2,5 | 0,8 | 7,41 | 7,41 | 7,98 |
4,0 | 0,8 | 4,61 | 4,61 | 4,95 |
6,0 | 0,8 | 3,08 | 3,08 | 3,30 |
10,0 | 1,0 | 1,83 | 1,83 | 1,91 |
16,0 | 1,0 | – | 1,15 | 1,21 |
25,0 | 1,2 | – | 0,727 | 0,780 |
35,0 | 1,2 | – | 0,524 | 0,554 |
50,0 | 1,4 | – | 0,387 | 0,386 |
70,0 | 1,4 | – | 0,268 | 0,272 |
95,0 | 1,6 | – | 0,193 | 0,206 |
120,0 | 1,6 | – | 0,153 | 0,161 |
* PV-1 – flexibility class 1. ** PV-2 – flexibility class 2. *** PV-3 – flexibility class 5. |
Brands of wires | Name of wires and their elements | The predominant usage |
PV1 | Installation wire with copper strand (single-wire), with polyvinyl chloride isolation | For not flexible installation of electrical circuits |
PV2 | Installation wire with copper strand (multi-wire), with polyvinyl chloride isolation, flexible | For installation of electric circuits on sites where bends of wires are possible |
PV3 | Installation wire with copper strand (multi-wire), with polyvinylchloride isolation, with increased flexibility | For installation of electrical circuits in areas where frequent bending of wires during installation is possible. |
PV1ng | Installation wire with copper strand (single-wire), with polyvinyl chloride isolation, with reduced flammability | For not flexible installation of electric circuits where the increased requirements to not spreading of burning are shown |
PV2ng | Installation wire with copper strand (multi-wire), with polyvinyl chloride isolation of reduced flammability, flexible | Similar to PV1ng for areas where bending of wires is possible |
PV3ng | Installation wire with copper strand (multi-wire), with polyvinyl chloride isolation of reduced flammability, with increased flexibility | Similar to PV2ng for areas where frequent bending of wires during installation is possible. |