KVBbShv, KVBbShvng

TU U 27.3-38456790-024:2022
Control cables
KVBbShv, KVBbShvng

Сontrol armoured cables with copper cores (Class 1), polyvinylchloride insulation and sheath
K Control cable
V Polyvinylchloride plasticate insulation
Bb Steel tape armour
Shv Polyvinylchloride plasticate protective hose
ng Non-combustible
ng-LS Non-combustible, reduced smoke and gas release

Operating and installation requirements

  • Ambient temperature from -50°C to 50°C.
  • Relative humidity up to 98% at temperatures up to 35°C.
  • Cables can be laid without preheating at temperatures not lower than –15°C.
  • Minimum bending radius during installation should be not less than 6 cable outer diameters.
  • Long-term temperature rise limits for cable cores should not exceed 70°C.
  • Temperature limit in the overload mode is max 90°C.
  • Rated alternating voltage up to 0.66 kV and up to 1kV.
  • Warranty service life is 5 years.
  • Service life is minimum 15 years.

Wires intended use
KVBbShv, KVBbShvng

Cables are intended for fixed connection to electrical devices, instruments, terminal boards of electrical switchgear rated up to 1 kV AC voltage and up to 100 Hz frequency.

Control armoured cables are used for laying in the ground (in trenches), premises and cable structures where protection against mechanical damage is required and no significant tensile forces are present.

Conductor design
KVBbShv, KVBbShvng

Core count Nominal voltage, V
0,66/1
Main cores nominal cross-section, mm2
2, 3, 4, 5, 7, 10, 14, 19 1, 1,5, 2,5
4, 5, 7 4

Design data for
KVBbShv, KVBbShvngwires

Core nominal cross-section, mm2 Nominal thickness, mm Nominal cable diameter, mm Maximum cord resistance at 20°C, Ohm/km Minimum value of insulation resistance at 20°C, MOhm/km Calculated mass of 1 km cable, kg
insulation sheath KVBbShv
2х1 0,6 1,2 7,1 18,1 10 201
2х1,5 0,6 1,2 7,5 12,1 10 224
2х2,5 0,6 1,2 8,3 7,41 9 261
3х1 0,6 1,2 7,4 4,61 10 225
3х1,5 0,6 1,2 7,9 12,1 10 252
3х2,5 0,6 1,2 8,8 7,41 9 303
4х1 0,6 1,2 8,1 18,1 10 252
4х1,5 0,6 1,2 8,6 12,1 10 285
4х2,5 0,6 1,2 9,6 7,41 9 350
4х4 0,7 1,3 11,3 4,61 9 461
5х1,5 0,6 1,2 9,3 12,1 10 325
5х2,5 0,6 1,3 10,6 7,41 9 411
5х4 1,0 1,4 14,1 4,61 9 533
5х6 1,0 1,4 15,5 3,08 6 674
7х1 0,6 1,3 9,7 18,1 10 323
7х1,5 0,6 1,3 10,3 12,1 10 387
7х2,5 0,6 1,3 11,5 7,41 9 487
7х4 0,7 1,3 13,4 4,61 9 647
10х1 0,6 1,4 12,2 18,1 10 431
10х1,5 0,6 1,4 13,0 12,1 10 507
10х2,5 0,6 1,4 14,6 7,41 9 646
14х1 0,6 1,4 13,2 18,1 10 431
14х1,5 0,6 1,4 14,1 12,1 10 607
14х2,5 0,6 1,4 15,8 7,41 9 793
19х1 0,6 1,4 14,6 18,1 10 610
19х1,5 0,6 1,4 15,6 12,1 10 749
19х2,5 0,6 1,4 17,6 7,41 9 981

Note: Calculated and nominal data can deviate from the actual data.
Identification markings meet fire safety requirements under DSTU 4809:2007
KVBbShv – PB 100000000
KVBbShvng – PB 120000000
KVBbShvng-LS – PB 123111000