YDYp(zo)

PN-E-90068:2016-10
Standard multicore round and flat cables for permanent wiring with thermoplastic PVC insulation
YDYp(zo)

Y Polyvinylchloride plastic insulation
D Copper core cable (Class 1)
Y Polyvinylchloride plastic coating
p Flat
zo Yellow-green protective conductor

Operating and installation requirements

  • Ambient temperature from -50°C to 50°C.
  • Relative humidity up to 98% at temperatures up to 35°C.
  • Cables can be laid without preheating at temperatures not lower than –15°C.
  • Minimum bending radius during installation should be not less than 10 outer diameters of a single core cable and 7.5 outer diameters of a multi-core cable.
  • Long-term temperature rise limits for cable cores should not exceed 70°C.
  • Temperature limit in the overload mode is max 90°C.
  • Rated alternating voltage up to 450/750 V.
  • Warranty service life is 5 years.
  • Service life is minimum 30 years

Wires intended use
YDYp(zo)

Cables are intended for transmission and distribution of electric power in permanent equipment for 450/750 V nominal AC voltage and 50 Hz frequency. It is recommended to use the given cable type for concealed wiring and individual laying in rectangular cable ducts of appropriate dimensions. Not recommended to be laid in the ground (in trenches).

Conductor design
YDYp(zo)

  Core count Rated voltage, V Backbone cores nominal cross-section, mm2

YDYp(zo)

2, 3 450/750 1,5 - 6

Design data for
YDYp(zo)wires

Core nominal cross-section, mm2 Nominal thickness, mm Maximum outer cable size, mm Maximum wire resistance at 20°C, Ohm/km Minimum value of insulation resistance at 20°C, MOhm/km Calculated mass of 1 km cable, kg
insulation sheath height width YDYp (zo)
2х1,5 0,8 1,2 5,0 7,5 12,1 12 71
2х2,5 0,8 1,2 5,4 8,3 7,41 10 94
2х4 0,9 1,2 6,2 9,8 4,61 9 138
2х6 0,9 1,3 6,9 11,2 3,08 7 189
3х1,5 0,8 1,2 5,0 10,1 12,1 12 101
3х2,5 0,8 1,2 5,4 11,3 7,41 10 136
3х4 0,9 1,2 6,2 13,4 4,61 9 201
3х6 0,9 1,3 6,9 15,5 3,08 7 277

Note: Calculated and nominal data can deviate from the actual data.
Identification symbols according to fire safety requirements as per PN-EN 50575+A1:2016 YDYp(zo) Eca